Intelligent Chart Recorder DS 500 for compressed Air and Gases

From recording and displaying measured data on a large color screen to issuing alerts, storing data, and offering remote read-out capabilities via a webserver, all of this is achievable with the DS 500. Through the CS Soft Basic software, alerts can be sent via SMS or email. All measured values, curve progressions, and threshold exceedings are displayed. The progression of curves from the beginning of the measurement can be reviewed with a simple slide of the finger.

Daily/WeeklyMonthly reports complete the sophisticated system concept, detailing costs in € and meter readings in m³ for each consumption sensor. The substantial difference between the DS 500 and ordinary paperless chart recorders lies in the ease of initiation and evaluation of the measured data. All sensors are directly identified and powered by the DS 500, resulting in a system that is perfectly harmonized and tuned.

TECHNICAL DATA DS 500

Dimensions of housing: 280 x 170 x 90 mm, IP 65
Connections: 18 x PG for sensors and supply
Version panel mounting: Cutout panel 250 x 156 mm
Weight: 3,5 kg
Material: Die cast metal, front screen polyester
Sensor inputs: • 4/8/12 sensor inputs for analogue and digital sensors; freely allocatable. See options

• Digital CS sensors for dew point and consumption with SDI interface FA/VA series,

• Digital third-party sensors RS 485 / Modbus RTU, other bus systems realizable on request.

• Analogue CS Sensors for pressure, temperature, clamp-on ammeters pre-configured.

• Analogue third-party sensors 0/4…20 mA, 0…1/10/30 V, pulse, Pt 100 / Pt 1000, KTY

Voltage supply for sensor: 24 VDC, max. 130 mA per sensor, integrated mains unit max. 24 VDC, 25 W. In case of version 8/12 sensor inputs, 2 integrated mains units each max. 24 VDC, 25 W.
Interfaces: USB stick, Ethernet / RS 485 Modbus-RTU / TCP, SDI other bus systems on request, webserver optional
Outputs: • 4 relays (changeover contact 230 VAC, 6 A), alarm management, relays freely programmable, collective alarm

• Analog output, pulse in case of sensors with own signal output looped, such as e.g. VA/FA series

Memory card: Memory size 16 GB Micro SD card
Power supply: 100…240 VAC / 50-60 Hz, special version 24 VDC
Colour screen: 7″ touch panel TFT transmissive, graphics, curves, statistics
Accuracy: See sensor specifications
Operating temperature: 0…50 °C
Storage temperature: -20…70 °C
Optional: Web server
Scroll to Top