Mobile active/reactive power meter CS PM 600

The CS PM 600 is available with a maximum capacity of either 100 A or 600 A. It measures voltage and current, and computes the following parameters:

  • Active power [kW]
  • Apparent power [kVA]
  • Reactive power [kVar]
  • Active energy [kWh]
  • Power factor (cos phi)

All the measured data are digitally transmitted via Modbus to the DS 500 mobile/ DS 400 mobile, where they can be recorded.

The CS PM 600 comes with special features that include:

  • Magnetic voltage measuring tips that allow voltage measurement during operation.
  • Hinged current transformers that can encircle the conductors of the phases L1, L2, L3, even while in operation.

 

TECHNICAL DATA CS PM 600

Parameters: Voltage (Volt)

Current (Ampere)

Cos phi

Effective power (kW)

Apparent power (kVA)

Reactive power (kVar)

Active energy (kWh)

Power frequency (Hz)

All parameters are transferred digitally to DS 500

mobile /DS 400 mobile

Accuracy current measurement: Threshold values for current deviation. Loss angle according to IEC 60044-1.

Current deviation in % at rated current in

120%   1

100%   1

20%     1.5

5%       3

Accuracy active

energy:

IEC 62053-21 Class 1
Sensor connections: 3 x current transformers (L1,L2,L3,N)

4 x voltage measurement (L1,L2,L3,N)

Interfaces: RS 485 (Modbus protocol)
Measuring range: Voltage measurement max. 400 Volt

Current measurement max. 100 A or 600 A

Size current transformers: 100 A / 1 A (max. 24 mm wire),

600 A / 1 A (max. 36 mm wire)

Dimensions case: 270 x 225 x 156 mm (B x H x T)
Operating temperature: – 10…+40 °C
Scroll to Top